AC motors are commonly paired with variable frequency drives (VFDs), which control motor speed by regulating the frequency of the supplied voltage. Depending on the application and level of speed regulation required, VFDs can be controlled by either scalar or vector methods. The most common type of VFD control is a scalar method referred to as volts per hertz (V/Hz) or volts per frequency (V/f).

  1. V/f Control Method Of Ac Drive
  2. V/f Control Method Of Induction Motor

The terms variable frequency drive (VFD) and variable speed drive (VSD) are often used interchangeably, but there is a distinction between the two.

A variable speed drive (VSD) is any drive that can control the speed of a piece of equipment, including both AC and DC motors. VSDs can operate via mechanical, hydraulic, or electrical means.

Methods

The VFC-9-200-2 Feeder Cube is a triple control for operating a vibratory bowl with a storage hopper and an inline. Unit A is a VF-9 variable frequency controller and units B & C are FC-200 fixed frequency digital controllers. Input voltage is 120VAC, 50/60 Hz. Output for Unit A is fused for 9 amps, Units B and C are fused for 5 amps each. Vector Control Of the above mentioned methods, V/f Control is the most popular and has found widespread use in industrial and domestic applications because of its ease-of-implementation. However, it has inferior dynamic performance compared to vector control. Thus in areas where precision is required, V/f Control are not used.

A variable frequency drive (VFD) is used to control the speed of AC motors, and does so by varying the frequency of the supply voltage to the motor.

How V/Hz control works

AC motors are designed for a magnetic field (flux) of constant strength. The magnetic field strength is proportional to the ratio of voltage (V) to frequency (Hz), or V/Hz. But a VFD controls the motor speed by varying the frequency of the applied voltage, according to the synchronous speed equation:

Vf Control Method

N = 120*f / P

Where:

N = motor speed (RPM)

f = input voltage frequency

P = number of motor poles

Motor

V/Hz control maintains a constant ratio between voltage (V) and frequency (Hz).
Image credit: Square D

Varying the voltage frequency affects both the motor speed and the strength of the magnetic field. When the frequency is lowered (for slower motor speed), the magnetic field increases, and excessive heat is generated. When the frequency is increased (for higher motor speed), the magnetic field decreases, and lower torque is produced. In order to keep the magnetic flux constant, the V/Hz ratio must remain constant. This keeps torque production stable, regardless of frequency.

V/Hz control of a VFD drive avoids this variation in the magnetic field strength by varying the voltage along with the frequency, in order to maintain a constant V/Hz ratio. The appropriate V/Hz ratio is given by the motor’s rated voltage and frequency. For example, a motor rated for 230 V and 60 Hz will operate best at a V/Hz ratio of 3.83 at all times (230/60 = 3.83).

Traditional V/Hz control does not use feedback, and only changes the voltage and frequency to the motor based on an external speed command. For closed-loop V/Hz control, encoder feedback can be added to measure the motor’s actual speed. An error signal is generated based on the difference between actual speed and commanded speed, and the controller generates a new frequency command to compensate for the error. While it improves speed regulation, closed-loop V/Hz control isn’t common due to the added cost and complexity of the encoder and feedback hardware.

Drive

Performance and benefits of V/Hz control

V/Hz control is a simple, low-cost method for controlling variable frequency drives, and is generally regarded as the most common VFD control scheme. It is suitable for both constant torque and variable torque applications and can provide up to 150 percent of the rated torque at zero speed for startup and peak loads. Speed regulation is in the range of 2 to 3 percent of the maximum rated frequency, so this method isn’t suitable for applications where precise speed control is critical. The most common use for V/Hz control is to drive industrial equipment such as fans and blowers.

V/f Control Method Of Ac Drive

One unique benefit of V/Hz control over other methods is that it allows more than one motor to be operated by a single VFD. All the motors will start and stop at the same time, and they will all run at the same speed, which is beneficial in some processing applications, such as heating and cooling.

The V/Hz control method allows one VFD to control four motors in a cooling tower.
Image credit: variablefrequencydrive.org

V/f Control Method Of Induction Motor

V/F control was the original methodology developed by AC drives manufacturers. One of the weaknesses in V/F drive is starting torque and lack of control. Vector control methodology was developed in the 80s to give better control at lower frequencies but could not go to zero speed. Therefore a third methodology, Field Control, was developed that can give full torque at zero speed.
A fan application does not need torque at zero speed and really normally (unless very large) need much torque at very low speeds. A V/F drive will do fine as will a vector drive. Efficiency should be similar in both technologies. Due to volume, cost is probably similar. All ac drive manufacturers still have V/F technology for multi-motor applications. Both vector and field methodologies must have a single load, if multiple motors are used V/F must be used.
It is the best way to try it. Set a fan drive in V/F mode and measure motor current, and set in vector control mode and measure the motor current in same mechanical environment. Lower current draw in open loop vector on the same application (high inrush current application), the drives controlling the current more precisely in open loop vector mode.
Also, as a side note, most ac drives now have energy savings mode which will adjust the acceleration to keep current low while getting up speed (different AC drives manufacturers do this in different ways), as opposed to following the defined ramp, as most fans are not critical acceleration so you may consider turning on this function for additional cost savings, the larger the motor the more the savings.